CISA Confirms Attacks on Three Danfoss AK-SM 800A Refrigeration Controller Flaws

Red Tiger Security infographic: CISA confirms attacks on three Danfoss AK-SM 800A refrigeration controller flaws, added to the Known Exploited Vulnerabilities catalog on 25 November 2026. CVE-2023-25915, command execution with a login, fixed in 3.3, score 9.9, due 28 November. CVE-2023-25914, system file reads through the XML interface with a login, fixed in 3.3, score 8.8, due 28 November. CVE-2025-41450, web report leaks internal addresses, usernames and store names, versions before 4.2, score 8.2, due 9 December. The flaws are old and have fixes, but CVE-2026-129713 needs no login and is still unpatched through 5.4.0, so exposure is the real risk. Steps: find every controller, take them off the internet behind a secure gateway and firewall, fix passwords, check for tampering. No primary source ties these CVEs to a specific group.

On 25 November 2026, the Cybersecurity and Infrastructure Security Agency (CISA) added three flaws in the Danfoss AK-SM 800A series to its Known Exploited Vulnerabilities (KEV) catalog, the agency's list of flaws that attackers are using in the real world. The AK-SM 800A is the refrigeration system manager that runs case temperatures, compressor racks and defrost schedules in supermarkets, cold storage warehouses and food distribution sites. These are the first Danfoss flaws in the KEV catalog, and the first time CISA has confirmed that attackers are using specific Danfoss controller flaws during the refrigeration controller campaign the Red Tiger team has been tracking since October.

The three flaws

  1. CVE-2023-25915, improper input validation. According to CISA, a remote attacker can run their own commands on the controller. The CVE record, published in August 2023 by the Dutch Institute for Vulnerability Disclosure (DIVD), says the attacker needs a login, rates it 9.9 out of 10 on version 3.1 of the Common Vulnerability Scoring System (CVSS), and lists versions before 3.3 as affected. Federal due date: 28 November 2026.
  2. CVE-2023-25914, path traversal, a flaw that lets an attacker step outside the folders the web interface is meant to serve. CISA says an attacker can read system files on the controller through its Extensible Markup Language (XML) interface. The CVE record also says the attacker needs a login, warns that what can be read can lead to a full system compromise, rates it 8.8, and lists versions before 3.3 as affected. Federal due date: 28 November 2026.
  3. CVE-2025-41450, improper authentication. CISA says an attacker can generate a web report that exposes internal network addresses, usernames and store names. Danfoss's own CVE record, published May 2025, rates it 8.2 and lists AK-SM 8xxA series versions before 4.2 as affected. Federal due date: 9 December 2026.

What is new

These are not new bugs. DIVD and Danfoss published the two 2023 flaws with a fix in version 3.3, and Danfoss published the 2025 flaw with versions before 4.2 listed as affected. What changed today is that CISA now has evidence attackers are using all three. CISA lists ransomware use as unknown and, for the two 2023 flaws, asks federal agencies to check for signs of compromise as well as patch. CISA does not say who is exploiting the flaws or where, and no primary source we have read ties them to a specific group, including the Iranian unit France named for the October attacks. We are not making that link.

How this fits the campaign

CERT-FR, France's national computer emergency response team, reported numerous compromises of Danfoss AK-SM and AK-SC controllers in October. France later attributed the October attack on about 700 grocery sites to a unit of Iran's Islamic Revolutionary Guard Corps (IRGC), and United States agencies issued a joint fact sheet on refrigeration and cold chain systems on 5 November. Belgium warned of six unpatched AK-SM800A flaws on 12 November, and CISA published CVE-2026-129713, a login-free flaw with no fix yet, on 24 November. Today's listing means owners now face both old flaws that attackers are using and new flaws that cannot be patched yet.

Earlier Red Tiger advisories:

Where these controllers show up from the plant floor to the cloud

The system manager usually sits in a back room or plant room, wired to compressors, evaporators and case sensors. Above it, the refrigeration service contractor often reaches it through a cellular modem or a direct internet address, and data may flow to a monitoring service in the cloud. That contractor path is often outside the asset inventory and firewall rules the plant or store team owns. The same pattern shows up in food and beverage plants, pharmaceutical cold chain, and cold rooms inside terminals and ports.

What to do now

  1. Find every Danfoss AK-SM 800A series controller, including ones your contractor connected through their own modem, and record its software version. Anything older than 4.2 is affected by at least one of today's flaws, and anything older than 3.3 by all three.
  2. Take the controllers off the internet now. Put remote access behind a secure, up-to-date virtual private network (VPN) gateway or private cellular network, behind a firewall and apart from business networks. Updating closes these three flaws, but CVE-2026-129713 is still unpatched through version 5.4.0, so updating alone is not enough.
  3. Change default and shared passwords and remove accounts nobody uses. Two of these flaws need a login, and the third exposes usernames.
  4. Treat any controller that was reachable from the internet on an old version as possibly compromised. Check setpoints, defrost schedules, user accounts and remote access settings, and set alarms for unexpected defrost cycles or temperature changes.

Red Tiger has completed more than 500 operational technology (OT) security assessments and trained more than 4,500 people, and contractor-managed refrigeration and building equipment is one of the most common blind spots we find. During our onsite facility assessments, our team walks the system from the perimeter through the demilitarized zone (DMZ) and control room down to the field devices, including contractor modems and remote access paths. We can then help remediate what we find, install a firewall and sensor at the site, connect them to the Red Tiger 24x7 security operations center (SOC), and monitor the site for ongoing detection and response, with regular metrics and reports.

We are here to help, so check out our resources online at www.redtigersecurity.com and book a follow-up call with our team if you have any questions: https://calendly.com/jonathanpollet/30min

Source: CISA Known Exploited Vulnerabilities catalog, version 2026.11.25: https://www.cisa.gov/known-exploited-vulnerabilities-catalog?search_api_fulltext=Danfoss

Source: CVE records CVE-2023-25915, CVE-2023-25914 and CVE-2025-41450 at https://www.cve.org

Source: DIVD case DIVD-2023-00025: https://csirt.divd.nl/cases/DIVD-2023-00025/