Slovenian Police Investigate Hack That Set a Meat Plant's Freezer to 100 Degrees Celsius

Red Tiger infographic: an intruder changed refrigeration setpoints at Salamerija Alpija in Tolmin, Slovenia, on 26 November 2026. A freezer was set to 100 degrees Celsius and two coolers to 20 degrees instead of 2 to 3; about 250,000 euros of meat was at risk and none spoiled. Before: alarms watched only measured temperature, the system was reachable from the internet, and the technician's login showed a taunt picture. After: take controllers off the internet behind a virtual private network with multi-factor login, alarm on setpoint and limit changes, change passwords and remove old accounts, and keep a manual-control playbook.

Police in Slovenia are investigating a cyberattack on the refrigeration system of a meat processing plant. On 26 November 2026, someone got into the internet-connected remote management system that controls the freezers and cold rooms at Salamerija Alpija, the salami plant of the Tolmin agricultural cooperative (Kmetijska zadruga Tolmin), and changed the temperature settings. A freezer chamber was set to 100 degrees Celsius, and coolers in the cooperative's slaughterhouse and in one of its shops were set to 20 degrees Celsius instead of the normal 2 to 3 degrees. Staff caught it by chance before the temperatures actually rose, and the cooperative says none of the meat, worth about 250,000 euros, was spoiled.

What happened

According to the cooperative's director, Nikola Šavle, speaking to the Slovenian news site 24ur.com, an employee doing a routine check around noon noticed the freezer setpoint (the target temperature the controller tries to hold) of 100 degrees. Because staff knew about the recent attacks on refrigeration systems in other European countries, they suspected a cyberattack right away and checked their other sites, where they found the slaughterhouse and shop settings. When the cooperative's refrigeration service technician tried to log in to the supervisory system, the login was blocked and the screen showed a picture of the Italian minister Matteo Salvini with the Italian caption "thank Uncle Matteo." The cooperative disconnected all of its refrigeration systems from the internet and set the temperatures by hand. It has added manual checks of the temperature settings every few hours.

The most important detail for plant owners is why no alarm went off. The director explained that the system raises an alarm when the temperature changes unexpectedly, but because someone changed the setting itself in the digital system, no warning was sent. He also asked what would have happened if the attack had come on a weekend, when nobody is in the plant.

On 27 November, the Nova Gorica Police Administration said it is investigating a suspected criminal attack on an information system. Police said early information points to unauthorized access to the remote management system for the refrigeration and freezer equipment, which stopped working correctly because of the changed temperature settings, and that access to the supervisory system was blocked. The company's maintainers disabled web access to the systems and then restored normal operation. Police said there was no material damage because staff responded quickly.

The cooperative reported the incident to SI-CERT, Slovenia's national computer emergency response team, which confirmed to the business newspaper Lider that it received the report on 26 November and that the investigation is ongoing. On 27 November, SI-CERT published security notice TZ018, "Protecting devices on the network," with 15 recommendations for owners of refrigeration systems and other remotely managed equipment. Nobody has claimed the attack, the method of entry has not been made public, and no agency has tied it to any group. The cooperative has not named the make of its refrigeration controller, and neither do we.

How it fits the wider picture

Since October 2026, attackers have changed settings on internet-exposed refrigeration controllers at hundreds of stores and food sites in France and across Europe, and Slovenia's Government Information Security Office warned Slovenian organizations about those incidents on 7 November. No source has confirmed a link between the Tolmin attack and those waves. Separately, on 25 November the Cybersecurity and Infrastructure Security Agency (CISA) added three flaws in Danfoss AK-SM 800A refrigeration controllers to its Known Exploited Vulnerabilities (KEV) catalog. There is no reported connection between that listing and this incident.

Earlier Red Tiger advisories on refrigeration controller attacks:

What it means for OT owners

Refrigeration controllers are operational technology (OT). The same kind of supervisory system runs cold rooms in food and beverage plants, cold chain warehouses, pharmaceutical storage, chemical cold storage and the chemical storage rooms at some water and wastewater plants. These systems are often installed and remotely managed by an outside refrigeration contractor, so they tend to sit outside the plant's asset list and firewall rules. Tolmin also shows a gap that many control systems share: alarms that only watch the measured temperature will stay quiet while someone quietly changes the setpoint, and the product only starts to warm up later, possibly on a night or weekend when nobody is walking the floor.

What to do now

  1. Take refrigeration and building controllers off direct internet exposure. Put remote access behind a virtual private network (VPN) with multi-factor authentication (MFA), and have contractors connect through access you control and can switch off, not through their own always-on connection.
  2. Add alarms for any change to a setpoint, defrost schedule or alarm limit, and set fixed high and low temperature limits that do not move when the setpoint moves. Where you can, add an independent temperature sensor with its own alerting path, as SI-CERT recommends.
  3. Change default passwords, and review every remote account, including contractor accounts. Remove the ones nobody uses, and keep a known good copy of each controller's configuration to compare against.
  4. Write a short playbook for running refrigeration by hand: who disconnects the remote link, who sets temperatures locally, and who checks them on nights and weekends until the system is trusted again.

Red Tiger has completed more than 500 OT security assessments and trained more than 4,500 people. During our plant-safe assessments, we walk the system from the perimeter through the demilitarized zone (DMZ) and control room down to the field devices, and that includes the refrigeration and building controllers that a contractor reaches from outside. We can then help close what we find, install a firewall and sensor at the site, connect them to the Red Tiger 24x7 security operations center (SOC), and monitor the site for ongoing detection and response, with regular metrics and reports.

We are here to help, so check out our resources online at www.redtigersecurity.com and book a follow-up call with our team if you have any questions: https://calendly.com/jonathanpollet/30min

Sources: RTV SLO and STA, Nova Gorica Police Administration statement, 27 November 2026 (Slovenian): https://www.rtvslo.si/crna-kronika/policisti-preiskujejo-kibernetski-napad-na-hladilnike-alpije/801530 ; 24ur.com, 26 November 2026 (Slovenian): https://www.24ur.com/novice/slovenija/hekerski-napad-na-hladilnike.html ; SI-CERT security notice TZ018, 27 November 2026 (Slovenian): https://www.cert.si/tz018/ ; Lider.si, SI-CERT confirmation, 27 November 2026 (Slovenian): https://lider.si/kz-tolmin-s-164-zaposlenimi-prijavila-kibernetski-incident-v-hladilnikih-si-cert-svetuje-15-ukrepov/ ; Slovenian Government Information Security Office, 7 November 2026 (Slovenian): https://www.gov.si/novice/2026-11-07-evropske-institucije-opozarjajo-na-kibernetske-incidente-v-hladilnih-sistemih/