November 17, 2026
← All advisories

Dorsett Controls InfoScan Water SCADA Flaws Give Away System Details

Red Tiger Security infographic titled Water SCADA Servers Are Telling Strangers Too Much, about Dorsett Controls InfoScan 1.45.0 and earlier, fixed in 1.46, from CISA advisory ICSA-26-321-01, 17 November 2026. A cross-section shows three zones. Outside the plant: web addresses answer with no login and reveal usernames, login settings, firmware and the BACnet/IP port; the public installer lists hostnames; bad login requests return internal file paths. Plant network: the desktop client accepts bad certificates so someone could pose as the server, highest score 8.1; the database password can be recovered from the registry; one template address skips the login check. Field: lift station and tank hardware is not directly affected, but its details are what the server gives away. Four steps: update to 1.46, close outside access with a VPN, lock down logins and change passwords, and firewall the SCADA network from the office network.

The Cybersecurity and Infrastructure Security Agency (CISA) published advisory ICSA-26-321-01 on 17 November 2026 covering six vulnerabilities in InfoScan, the supervisory control and data acquisition (SCADA) system that Dorsett Controls builds for water, stormwater and wastewater systems, along with building controls. Every InfoScan release up to and including version 1.45.0 is affected, and Dorsett Controls has fixed them in version 1.46. CISA lists Water and Wastewater Systems as the affected critical infrastructure sector, with installations worldwide. The most serious flaw scores 8.1 out of 10 on the Common Vulnerability Scoring System (CVSS). CISA says no known public exploitation of these vulnerabilities has been reported.

What the vulnerabilities are

None of these six flaws lets someone take over a pump station on its own, but together they hand an outsider most of what they would need to plan an attack, and one of them makes it easier to intercept the operator's connection.

  1. CVE-2026-117659 (CVSS 8.1): the InfoScan desktop client accepts security certificates it should reject when it connects to the server, and it runs with several built-in browser safety settings switched off. Someone who can sit in the middle of the network connection could pose as the server without the client refusing the connection.
  2. CVE-2026-120157: the publicly distributed desktop installer contains configuration files with hostnames tied to customer installations and to Dorsett's own development, test and database systems. Anyone who downloads and opens the installer can read them.
  3. CVE-2026-120255: InfoScan encrypts its database password with a key that is built into the software itself, then stores it in the Windows registry. Someone with access to that registry value and a copy of the program could recover the database password.
  4. CVE-2026-120260: one web address used to retrieve templates does not check for a login, so a local user without a valid session can pull data from it.
  5. CVE-2026-120271: two web addresses used by the mobile app and for version reporting answer without a login. They give back usernames and display names, whether multifactor authentication (a second login step beyond the password) is turned on, session settings, software and server details, firmware versions of the field hardware modules, and the BACnet/IP port (the building and plant automation network protocol) the system uses.
  6. CVE-2026-120298: malformed login and password-reset requests cause the server to return detailed error messages that reveal internal folder paths, file names and line numbers in the program.

Where this shows up, plant floor to cloud

Red Tiger's view is that the information leaks matter more than their individual scores suggest. InfoScan is sold to utilities for its web and mobile access, so operators can check lift stations, tank levels, generators and alarms from a phone. That convenience usually means the InfoScan server can be reached from outside the plant, either straight from the internet or through a port someone opened years ago. A server that answers strangers with its list of user accounts, whether those accounts use a second login step, and the firmware versions of the field hardware is giving away a map of the system. For a small district or city water department, where the SCADA server may also sit on the same network as office computers, that map is the first thing an attacker looks for. The desktop client flaw matters most on shared or flat networks, such as a treatment plant where the operator workstation, the SCADA server and the office share one network with no firewall between them.

What to do now

  1. Update every InfoScan system to version 1.46 or later. Dorsett Controls says administrators can log in, open System Maintenance, choose Check for Updates and click Install Now. Systems without internet access can get the update from the Dorsett Controls Customer Portal under the InfoScan Update tile. Schedule the update with your operators and confirm alarming and remote access work afterward.
  2. Find out how your InfoScan server is reached from outside. Ask whoever set up remote access whether the web or mobile service is open to the internet. If it is, put it behind a virtual private network (VPN) with multifactor authentication, or limit it to a short list of known addresses.
  3. Turn on multifactor authentication for every InfoScan account, remove old and shared logins, and change the database and administrator passwords after you update, since the old database password could be recovered from the registry.
  4. Put a firewall between the SCADA server and operator workstations on one side and the office network on the other, and keep the operator workstation's connection to the server on that protected network so nobody can intercept it.

Red Tiger can help with this beyond the assessment itself. We find exposed SCADA servers and remote access paths during our site walk-downs, fix and harden the weaknesses we find, and can install a firewall and sensor at the site, connect them to the Red Tiger 24x7 security operations center (SOC), and monitor the plant for ongoing detection and response, with regular metrics and reports.

We are here to help, so check out our resources online at www.redtigersecurity.com and book a follow-up call with our team if you have any questions: https://calendly.com/jonathanpollet/30min

Source: CISA ICS Advisory ICSA-26-321-01, Dorsett Controls InfoScan, 17 November 2026: https://www.cisa.gov/news-events/ics-advisories/icsa-26-321-01

← All advisories

Cite this advisory: Red Tiger Security, "Dorsett Controls InfoScan Water SCADA Flaws Give Away System Details", November 17, 2026, https://www.redtigersecurity.com/advisory/dorsett-infoscan-scada-water-wastewater-vulnerabilities

Read the original source →

We are here to help.

Check out our resources and book a follow-up call with our team.

+1.877.387.7733