November 23, 2026
← All advisories

WAGO, Wiesemann & Theis and ifm Advisories from CERT@VDE

Red Tiger Security infographic comparing three CERT@VDE advisories published 23 November 2026. WAGO VDE-2026-096: CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400; the web page lets a low-privileged user run root commands and change PROFIBUS settings; a login is needed; worst score 8.8 of 10; fix is firmware 4.10.0 FW32 or later, and 4.10.4 also closes PHP2Shell. Wiesemann and Theis VDE-2026-135: pure.box 3 and 5, Motherbox 4 and FTP Data Station 3 carry PHP2Shell in the built-in web server; no login needed; 9.8 of 10; fixed firmware 1.84, 2.00, 1.51 and 1.31; update or turn off the web server. ifm VDE-2026-148: O3D, O3DP and O3X camera sensors have an interface with no login check; 9.8 of 10; no fix available; put them in their own segment.

CERT@VDE, the German computer emergency response team that coordinates security advisories for European industrial automation vendors, published three new advisories on 23 November 2026. One covers WAGO controllers and panels, one covers Wiesemann & Theis devices that carry the PHP2Shell flaws, and one covers ifm camera sensors that have no fix yet. All three products show up on plant floors, in machine builder panels and in building and process automation.

WAGO: two privilege flaws in the web management page (VDE-2026-096)

WAGO's Web-Based Management (WBM) is the browser page used to set up its controllers. Two flaws let someone who already has a low-privileged login on that page go beyond what that login is supposed to allow.

  1. CVE-2026-80466 (Common Vulnerability Scoring System, or CVSS, score 8.8): the routing settings page does not properly check what is typed into it. Those values are later run by a helper script with full administrator (root) rights, so a low-privileged user can run commands as root on the controller.
  2. CVE-2026-88850 (CVSS 8.1): the page does not properly check permissions on PROFIBUS settings. A low-privileged user can change protected fieldbus settings, including device addresses.

Affected products are the CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400 running WAGO firmware earlier than 4.10.0 (FW32), including custom firmware builds. The fix is firmware 4.10.0 (FW32) or later. Customers on custom firmware need to contact WAGO support. If you already moved these devices to firmware 4.10.4 (FW32) for the WAGO PHP2Shell advisory we covered on 5 November, you already have this fix as well.

Wiesemann & Theis: PHP2Shell on pure.box, Motherbox and FTP Data Station devices (VDE-2026-135)

Wiesemann & Theis (W&T) is a German maker of industrial network and interface devices. Its devices that have the built-in web server turned on run an affected version of PHP, the scripting language behind the web page, and carry the two PHP2Shell flaws, CVE-2026-109618 (CVSS 9.8) and CVE-2026-109619 (CVSS 8.1). A specially crafted web request can let an attacker take over the web server process without logging in. PHP2Shell has been exploited in the wild and has been on the CISA (Cybersecurity and Infrastructure Security Agency) Known Exploited Vulnerabilities list since October. CERT@VDE does not report attacks on these W&T devices.

  1. pure.box 3, pure.box 3 USB, pure.box 3 Serial and pure.box 3 Serial / USB: affected before firmware 1.84, fixed in 1.84.
  2. pure.box 5 2xNW: affected before firmware 2.00, fixed in 2.00.
  3. Motherbox 4: affected before firmware 1.51, fixed in 1.51. (The advisory's remediation note calls it Motherbox 3; the product list says Motherbox 4.)
  4. FTP Data Station 3: affected before firmware 1.31. The machine-readable advisory lists 1.31 as fixed, and the remediation note points to 1.32 as the latest release on wut.de.

Until you can update, W&T says to turn off the device's web server from its web-based management.

ifm: no login needed on O3D, O3DP and O3X camera sensors, and no fix (VDE-2026-148)

ifm electronic makes sensors and machine vision products used on production lines and in logistics. CVE-2026-121613 (CVSS 9.8) is a missing login check on an interface of its camera sensors. Anyone who can reach that interface over the network can send it commands without logging in, force the sensor to reboot or load their own firmware onto it. Affected models listed are the O3D300 through O3D355 series, the O3D361, the O3DP01, O3DP03, O3DP21 and O3DP23, and the O3X120 and O3X130 on the firmware versions named in the advisory. ifm states no fix is available. Its guidance is to place the sensors in their own access-restricted network segment and allow only the connections they need with trusted systems.

Why this matters for plant owners: none of these advisories reports attacks on the devices themselves, but each one gives an attacker who is already on the plant network a short path to something that matters. A shared low-privileged WAGO login becomes root on a controller and a way to change fieldbus settings. A W&T device with its web page on is open to a flaw that attackers are already using elsewhere. An ifm sensor on a flat network can be rebooted or reflashed by anyone who can reach it, and a vision sensor that stops working or reports wrong results can stop a line or let bad product through.

What to do now

  1. Find them. Search your asset inventory and switch tables for WAGO CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400; W&T pure.box, Motherbox and FTP Data Station devices; and ifm O3D, O3DP and O3X sensors. Ask your machine builders and integrators which of these they shipped inside their panels.
  2. Update WAGO and W&T. Move WAGO devices to firmware 4.10.0 (FW32) or later, and preferably 4.10.4 to close PHP2Shell too. Move W&T devices to the fixed firmware listed above. If you cannot update W&T devices yet, turn off their web server.
  3. Wall off the ifm sensors. With no fix, put them in their own segment behind a firewall rule that allows only the vision controller, the PLC (programmable logic controller) and the engineering workstation that need them.
  4. Tighten web management logins. Remove shared and unused WAGO WBM accounts, give each person their own login, and allow the management pages only from the engineering network, never from the business network or the internet.

Red Tiger can help you find which of these devices are on your plant and which advisories apply. During our onsite facility assessments, our team walks the system from the perimeter through the demilitarized zone (DMZ) and control room down to the field devices, including the controllers and sensors that come inside machine builder panels. We can then help remediate and harden what we find, and we can install a firewall and sensor at the site, connect them to the Red Tiger 24x7 security operations center (SOC), and monitor the site for ongoing detection and response, with regular metrics and reports. Our team has completed more than 500 assessments and trained more than 4,500 people.

We are here to help, so check out our resources online at www.redtigersecurity.com and book a follow-up call with our team if you have any questions: https://calendly.com/jonathanpollet/30min

Source: CERT@VDE advisories VDE-2026-096 (WAGO), VDE-2026-135 (Wiesemann & Theis) and VDE-2026-148 (ifm), published 23 November 2026: https://certvde.com/en/advisories/

← All advisories

Cite this advisory: Red Tiger Security, "WAGO, Wiesemann & Theis and ifm Advisories from CERT@VDE", November 23, 2026, https://www.redtigersecurity.com/advisory/certvde-wago-wut-ifm-advisories

Read the original source →

We are here to help.

Check out our resources and book a follow-up call with our team.

+1.877.387.7733